Butinox - Optimal - Floor Varnish - Natural Wood Soap - Fire Proofing paint- Envirograf - jotun

Fire proofing paint - envirograf - uk building regulations - intumescent paint - FIRE PROTECTION

Email:

Tel: 01932 268440

TRUNKING WRAPS

All Electrical Products to comply with the revised 16th Edition of the IEE Regulations
and Document B of UK Building Regulations

DESCRIPTION
An intumescent trunking wrap, to fit around PVC trunking.

USE
Use wherever PVC electrical trunking passes through a block, brick, or concrete fire barrier wall or floor. The wrap is fitted around the trunking, and pushed into the wall or ceiling, so that in a fire the wrap expands and crushes the trunking. Can be used where PVC electrical trunking passes through plasterboard partitions or walls.

PERFORMANCE
This product underwent a fire resistance test employing the general procedures and criteria of BS476 Part 22 (1987), achieving an integrity of 130 minutes in solid walls, and 67 minutes in hollow walls. Also tested at VNE to European Standard EN1363-1 (2000).

ORDERING REFERENCES

TW State the size of trunking and the thickness of the wall

For friendly advice, please ring us! 01932 268440